f

314.16(B)(5) Box Fill Calculation Revised. Volume Allowance for EGCs and Equipment Bonding Jumpers

Revision

Change Summary

  • An additional ¼ volume allowance is now required to be added to the existing volume allowance of a single conductor volume allowance based on the largest equipment grounding conductor or equipment bonding jumper entering the box. This new ¼ volume allowance will be counted for each EGC installed in the box for more than four EGCs or equipment bonding conductors. This change eliminates the need to specifically address the EGCs for isolated ground receptacles permitted by 250.146(D).
NEC® Text

314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies.
Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. In no case shall the volume of the box, as calculated in 314.16(A), be less than the fill calculation as calculated in 314.16(B). The minimum volume for conduit bodies shall be as calculated in 314.16(C).
The provisions of this section shall not apply to terminal housings supplied with motors or generators.
Boxes and conduit bodies enclosing conductors 4 AWG or larger shall also comply with the provisions of 314.28.
Outlet and device boxes shall also comply with 314.24.

(B)Box Fill Calculations. The volumes in paragraphs 314.16(B)(1) through (B)(5), as applicable, shall be added together. No allowance shall be required for small fittings such as locknuts and bushings. Each space within a box installed with a barrier shall be calculated separately.
(5) Equipment Grounding Conductor Fill.
Where one or more up to four equipment grounding conductors or equipment bonding jumpers enter a box, a single volume allowance in accordance with Table 314.16(B) shall be made based on the largest equipment grounding conductor or equipment bonding jumper present in entering the box. Where an additional set of equipment grounding conductors, as permitted by 250.146(D), is present in the box, an additional A ¼ volume allowance shall be made for each additional equipment grounding conductor or equipment bonding jumper that enters the box, based on the largest equipment grounding conductor in the additional set or equipment bonding conductor.

Material taken from the National Electric Code® is reprinted with permission from NFPA 70®, 2020 edition.
National Electrical Code®, Copyright 2019, National Fire Protection Association, Quincy, MA. All rights reserved.

Expert Analysis

Volume of a box is the total volume in cubic millimeters or cubic inches of the assembled sections. This total volume (space) determines the number and size of conductors and wiring devices permitted to be contained in the box. Conductors, internal clamps, support fittings, and devices such as switches and receptacles take up space within the box. So, the Code assigns to each conductor, clamp, support fitting, device and equipment grounding conductor an associated volume allowance. This volume allowance is listed in cubic inches or cubic centimeters. Table 314.16(B) list the volume allowance as a function of conductor size. For example, according to Table 314.16(B), each 12 AWG conductor in a box takes up 36.9 cm3 (2.25 in.3) of free space within that box. When preforming a box fill calculation, the volume allowance for each conductor, clamp, support fitting, device, and equipment grounding conductor is added together. The box must have a volume that equals or exceeds the total volume required for the contained items.

314.16(B)(5) Box Fill Calculation Revised. Volume Allowance for EGCs and Equipment Bonding Jumpers

A single volume allowance has been required for all equipment grounding conductors within a box since the 1971 NEC. This single volume deduction was based on the largest equipment grounding conductor or equipment bonding jumpers present in the box. This was for all equipment grounding conductors or equipment bonding jumper regardless of the number of equipment grounding conductors or equipment bonding jumpers installed.

For the 2020 NEC, the single volume allowance or deduction will apply to the first four equipment grounding conductors or equipment bonding jumpers. Any equipment grounding conductor or equipment bonding jumper installed above four will require an additional ¼ volume allowance to the existing volume allowance of a single conductor volume allowance based on the largest equipment grounding conductor or equipment bonding jumper entering the box. In multiple gang boxes, taking only one volume allowance based on the largest EGC is not adequate in many cases resulting in significant undue crowding of conductors and not enough free space to allow heat to dissipate from the contained conductors. This change also eliminates the need to specifically address the equipment grounding conductors for isolated ground receptacles permitted by 250.146(D).

This revision to the required free space in a box for equipment grounding conductors and equipment bonding jumpers will address is the issue of complying with both 314.16(B)(5) and 300.14. The requirements of 300.14 generally require at least 150 mm (6 in.) of free conductor, measured from the point in the box where it emerges from its raceway or cable sheath, to be provided at each outlet, junction, and switch point for splices or the connection of luminaires or devices. Requiring all equipment grounding conductors to meet 300.14 (at least 150 mm (6 in.) of free conductor for each conductor) and applying only a single volume allowance was problematic in past editions of the Code in device boxes with multiple equipment grounding conductors and often resulted in overcrowded conditions.