f

312.8(B) Energy Management Equipment

Revision

Change Summary

  • The Code language at 312.8(B) expands allowances for wiring space of enclosures for switches or overcurrent devices to contain “power monitoring equipment” and “energy management equipment” under specific conditions along with smaller conductors used exclusively for control or instrumentation circuits of such equipment.
NEC® Text

312.8 Switch and Overcurrent Device Enclosures.
(B)Power Monitoring or Energy Management Equipment. The wiring space of enclosures for switches or overcurrent devices shall be permitted to contain power monitoring or energy management equipment where all of the following conditions are met: in accordance with 312.8(B)(1) through (B)(3).
(1)Identification. The power monitoring or energy management equipment is shall be identified as a field installable accessory as part of the listed equipment, or is a listed kit evaluated for field installation in switch or overcurrent device enclosures.
(2)Area. The total area of all conductors, splices, taps, and equipment at any cross section of the wiring space does shall not exceed 75 percent of the cross-sectional area of that space.
(3)Conductors. 
Conductors used exclusively for control or instrumentation circuits shall comply with either 312.8(B)(3)(a)or(B)(3)(b).
(a)Conductors shall comply with 725.49.
(b)Conductors smaller than 18 AWG, but not smaller than 22 AWG for a single conductor and 26 AWG for a multiconductor cable, shall be permitted to be used where the conductors and cable assemblies meet all of the following conditions:
  (1)Are enclosed within raceways or routed along one or more walls of the enclosure and secured at intervals that do not exceed 250 mm (10 in.)
  (2)Are secured within 250 mm (10 in.) of terminations
  (3)Are secured to prevent contact with current carrying components within the enclosure
  (4)Are rated for the system voltage and not less than 600 volts
  (5)Have a minimum insulation temperature rating of 90°C

Material taken from the National Electric Code® is reprinted with permission from NFPA 70®, 2020 edition.
National Electrical Code®, Copyright 2019, National Fire Protection Association, Quincy, MA. All rights reserved.

Expert Analysis

In response to the demand for such equipment being installed in a cabinet containing switches or overcurrent devices, the 2017 NEC adopted new text at 312.8(B) to allow “power monitoring equipment” within the wiring space of enclosures for switches or overcurrent devices with specific conditions including the limit on the amount of space occupied by all conductors, splices, taps, devices, and equipment to the same 75 percent fill requirement that was previously located at 312.8(2) [now 312.8(A)(2)].

312.8(B) Energy Management Equipment

For the 2020 NEC, CMP-9 took this requirement one step further by adding the term “energy management equipment” to this wiring space requirement. Both types of equipment present the same concern and is governed by the same product standards (UL Product Spec category XOBA). This category covers open-type current transformers intended for field installation within distribution and control equipment such as panelboards, switchboards, industrial control equipment, and energy-monitoring/ management equipment, to measure current on a branch circuit. Energy Management Equipment is also addressed by UL Product Spec category PAZX.

A new list item was also added at 312.8(B)(3) for conductors used exclusively for control or instrumentation circuits of equipment installed within these cabinet enclosures containing switches or overcurrent devices. Sensors associated with power monitoring and energy management equipment operate at very low current levels and smaller conductors which can introduce concern with the mechanical strength of the wire and its ability to withstand the wiring space environment. The new text provides two options for conductors. The first option references 725.49.

This section provides sizing and insulation requirements for Class 1 circuit conductors. The second option establishes use of smaller AWG conductors, along with specific construction and installation requirements to address suitability within the wiring space normally reserved for nominal power equipment such as overcurrent devices.

Leviton Solution
Equipment typically installed in cabinet enclosures for power monitoring typically include CTs (Current Transformers). The CTs encircle conductors and measure current flow and thus energy usage. The measurements are transmitted to a submeter where it is collected and turned into useful energy consumption data.

Organizations can monitor, control, and manage energy usage through submetering strategies, which track energy usage and power consumption for individual tenants, departments, and pieces of equipment or other loads to account for their actual energy usage.

From tenant billing to energy measurement & verification (M&V), Verifeye™ offers a seamless solution that enables smart metering and simplifies the complexities of monitoring energy usage, allocating energy costs and billing tenants.

312.8(B) Energy Management Equipment